J.Propster Surge arrester class II

Class II Surge arrestor 40kA – J.Propster

Category:
P-VM(S) (Fm) and P-N/PE C (S); (class II)//LPZ 1-LPZ 2
Surge arrester
 

 

Type

Max. continu- ous operating voltage

Uc

Voltage protection level

Up

Nominal discharge current

In (8/20 µs)

 

 

Old ord. no.

 

 

Ord. no.

P-VM 280; not pluggable 280 V~ < 1300 V 20 kA 2066 3066
P-VMS 280; pluggable 280 V~ < 1300 V 20 kA 206 280 306 280
Surge arrester, pluggable
Type Uc Up In (8/20 µs) Ord. no.
P-VMS 75 75 V~ < 600 V 15 kA 206 076 306 076
P-VMS 150 150 V~ < 950 V 20 kA 206 150 306 150
P-VMS 360 360 V~ < 1850 V 20 kA 206 361 306 361
P-VMS 440 440 V~ < 2000 V 20 kA 206 441 306 441
P-VMS 500 500 V~ < 2200 V 20 kA 206 501 306 501
P-VMS 600 600 V~ < 2400 V 20 kA 206 602 306 602
Surge arrester, pluggable, with remote signalling contact (Fm)
Type Uc Up In (8/20 µs) Ord. no.
P-VMS 280 Fm 280 V~ < 1300 V 20 kA 206 282 306 282
P-VMS 75 Fm 75 V~ < 600 V 15 kA 206 078 306 078
P-VMS 150 Fm 150 V~ < 950 V 20 kA 206 152 306 152
P-VMS 360 Fm 360 V~ < 1850 V 20 kA 206 365 306 365
P-VMS 440 Fm 440 V~ < 2000 V 20 kA 206 443 306 443
P-VMS 500 Fm 500 V~ < 2200 V 20 kA 206 503 306 503
P-VMS 600 Fm 600 V~ < 2400 V 20 kA 206 604 306 604
Surge arrester, not pluggable
Type Uc Up In (8/20 µs) Ord. no.
P-VM 75 75 V~ < 600 V 15 kA 206 075 306 075
P-VM 360 360 V~ < 1850 V 20 kA 206 360 306 360
P-VM 500 500 V~ < 2200 V 20 kA 206 500 306 500
Surge arrester, not pluggable, with remote signalling contact (Fm)
Type Uc Up In (8/20 µs) Ord. no.
P-VM 75 Fm 75 V~ < 600 V 15 kA 206 074 306 074
P-VM 280 Fm 280 V~ < 1300 V 20 kA 2067 3067
Surge arrester for TT-System
Type In (8/20 µs) Ord. no.
P-N/PE C 1-pole (not pluggable) 30 kA 206 285 306 285
P-N/PE C S 1-pole (pluggable) 30 kA 206 286 306 286

 

Technical data P-VM(S) P-N/PE C (S)
Dimensions 1 mod. 1 mod.
Max. continuous operating voltage Uc see above 255 V~
Nominal discharge current (8/20 µs) In see above 30 kA
Max. discharge current (8/20 µs) Imax 40 kA 60 kA
Voltage protection level Up see above < 1.5 kV
Response time tA < 25 ns < 100 ns
Max. backup fuse 125 A gL/gG
Cross section for connection min. 6 mm² single-core/ finely-stranded max. 50 mm² stranded / 35 mm² finely-stranded

Additional operating voltages on request.